Skip to catalogue results

Compare Inovance Options for FX5UJ-24MR/ES

Official distributor for Australia and New Zealand
Inovance AM521-0808TP-INT
Manufacturer illustration. Confirm the exact physical variant.

AM521-0808TP-INT

Why this option

  • 16 digital inputs for 14 published points
  • 12 relay outputs for 10 published points

Equipment to include 1 × GL20-0800END-INT · 1 × GL20-0008ER-INT · 1 more in the retrofit plan

Review Full Comparison
Edit Requirements

Confirm the supply, I/O wiring, network roles and programme migration.

Must stay
Retrofit Equipment, Checks and Manuals

What This Retrofit Needs

Equipment to Include

  • 1 × GL20-0800END-INT · Digital input module
  • 1 × GL20-0008ER-INT · Normally open relay output module
  • 1 × GL20-0004ER-INT · Normally open relay output module
  • Rebuild and validate the GX Works3 programme, then remap the installed inputs and outputs.
  • Provide a sized 24 V DC controller supply and update the panel wiring.

Checks Before Quoting

  • Check normally open contact wiring, DC or AC load and switching frequency. The GL20 relay has a 2 A resistive point limit. Use the per-module and thermal limits for the exact module and add separate switching where required.
  • Match the actual field input voltages, dedicated commons and programmed timing. Confirm 5 V expansion-bus load, cabinet space and terminal wiring.
  • Confirm the configured high-speed inputs, pulse axes, output commons and connected field devices. Replace installed Mitsubishi expansion and validate the programme before commissioning.
  • Verify the cabinet supply and field-signal wiring for the redesigned station.
  • The sourcing CPU publishes pulse input up to 100 kHz. Check installed pulse modes and timing.
  • Confirm input wiring, output loads, programme timing, installed expansion and active network roles.

Documents

Inovance signal-module specificationsPDFInovance controller specificationsPDFInovance AM320 / AM521 / AM522 — six CPU variants, memory, Ethernet topology and expansion limitsPDF

Full Specification Comparison

SpecificationFX5UJ-24MR/ES
DC supply
FX5UJ-24MR/ESNot listedAM521-0808TP-INT
21.6–26.4 V DC
AC supply
FX5UJ-24MR/ES100–240 V ACAM521-0808TP-INT
Not listed
Dimensions (W × H × D)
FX5UJ-24MR/ESNot listedAM521-0808TP-INT
53 × 100 × 80 mm
Digital inputs
FX5UJ-24MR/ES14AM521-0808TP-INT
8
Digital outputs
FX5UJ-24MR/ES10AM521-0808TP-INT
8
Digital output type
FX5UJ-24MR/ESRelayAM521-0808TP-INT
source
High-speed inputs
FX5UJ-24MR/ESNot listedAM521-0808TP-INT
8
Motion control
FX5UJ-24MR/ESNot listedAM521-0808TP-INT
8 axes
Expansion system
FX5UJ-24MR/ESNot listedAM521-0808TP-INT
16 local modules
Ethernet ports
FX5UJ-24MR/ES1AM521-0808TP-INT
2
Serial interface
FX5UJ-24MR/ESNot listedAM521-0808TP-INT
One onboard RS485. Up to two GE20 RS232/485 expansion cards; free protocol and Modbus RTU/ASCII. Additional GL20 serial modules are separate hardware.
Engineering software
FX5UJ-24MR/ESGX Works3AM521-0808TP-INT
InoProShop, based on CODESYS; software, runtime licences, libraries, hardware firmware and project migration require separate confirmation.

▲ and ▼ show numerical differences. Check supply, configuration and installation before choosing.

Brand names and part numbers are used only to identify the products being compared. Universal Systems is not affiliated with or endorsed by these manufacturers. Comparisons use published specifications and are a starting point, not a confirmed replacement. Our engineers confirm suitability before any order.