Suggested RetrofitEASY320-0808TP-INT
Why this option
- 16 digital inputs for 14 published points
- 16 sourcing outputs for 10 published points
- 2 analogue inputs covered by the stated configuration
Equipment to include 1 × GL20-0800END-INT · 1 × GL20-0008ETP-INT · 2 more in the retrofit plan
Edit Requirements
Retrofit Equipment, Checks and Manuals
What This Retrofit Needs
Equipment to Include
- 1 × GL20-0800END-INT · Digital input module
- 1 × GL20-0008ETP-INT · Sourcing transistor output module
- 1 × GL20-4AD-INT · Analogue input module
- 1 × GL20-4DA-INT · Analogue output module
- Rebuild and validate the TIA Portal programme, then remap the installed inputs and outputs.
- Confirm a 24 V DC panel supply within the Easy controller limits.
Checks Before Quoting
- Check field outputs at 21.6–26.4 V DC, 0.5 A resistive per point at most, and the lower of the published per-module limits for the exact output module. Confirm inductive, inrush and common loads.
- Match the actual field input voltages, dedicated commons and programmed timing. Confirm 5 V expansion-bus load, cabinet space and terminal wiring.
- The plan is for ordinary I/O and a programme rebuild. Check each configured high-speed counter, PTO axis, retained HMI, expansion module and PROFINET controller role. Existing PROFINET field devices require a separate migration review.
- Check which analogue points are used, their active modes, loop and voltage loads, impedance, filtering and scaling.
- Verify the cabinet supply and field-signal wiring for the redesigned station.
- Confirm the configured high-speed inputs and pulse axes, including wiring mode, output load and timing.
- Confirm input wiring, output loads, programme timing, installed expansion and active network roles.